Rectifiers & D.C. Power Supply Systems
D.c. supply systems for electrolysis and graphitization furnaces
Main specifications
| Parameter name
|
Value | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Electrolysis | Graphitization furnaces
| |||||||||||
| Al
| Cl
| Mg | Na, K | |||||||||
| Primary voltage, kV | 0 ÷ 220
| |||||||||||
| Current of one set, kA | 25 ÷ 100 | 50 ÷ 120 | ||||||||||
| Total current, kA | 100 ÷ 450 | 100 ÷ 300 | 100 ÷ 300 | 100 ÷ 200 | 50 ÷ 300 | |||||||
| Rectified voltage, V | 1500 | 450 ÷ 1000 | 200 ÷ 600 | 60 ÷ 200 | 100 ÷ 300 | |||||||
| Number of sets | 3 ÷ 9 | 3 ÷ 6 | 3 ÷ 6 | 2 ÷ 4 | 2 ÷ 4 | |||||||
| Rectification circuit diagram | Bridge | Bridge, two opposed star groups with interphase transformers | ||||||||||
| Pulse number of one set | 12 | |||||||||||
| Total pulse number | 24 ÷ 72 | |||||||||||
| Types of rectifiers | – diode;
– diode with saturable reactors; – thyristor | |||||||||||
| Accuracy of current maintaining, % | ± 1 | |||||||||||
| Voltage regulation
coarse fine | by no – load, on – load devices of transformer;
by saturable reactors, thyristor firing angle | |||||||||||
| Power factor (without compensation), not worse | 0,9 | |||||||||||
| Cooling of power semiconductors | non – freezing liquid – water;
non – freezing liquid – air | |||||||||||
| Installation | – indoors;
– outdoors | |||||||||||
| Ambient air temperature, °C | from -45 to +55 | |||||||||||
Delivery set:
- switchgear devices: outdoor 10 ÷ 220 kV;
- rectifier sets, pcs 3 ÷ 9 (n + 1);
- a.c. buses between transformer and rectifier;
- current meter of series up to 500 kA;
- automated current control system series ROSELCO MICROSCADA;
- filter compensating unit;
- d.c. buses assembly.
Engineering on "turnkey basis":
- designing, electric and construction works;
- fabrication and complete supply of equipment;
- contract supervision, erection works;
- start – up and adjustment works, commissioning;
- training of personnel;
- servicing.
Назад в раздел